• DocumentCode
    27294
  • Title

    Effect of environment factors on ac flashover performance of 3 units of polluted insulator strings under natural fog condition

  • Author

    Dong, Binhong ; Jiang, Xinyang ; Zhang, Zhenhao ; Hu, Jiankun ; Hu, Qin ; Shu, Lei

  • Author_Institution
    State Key Laboratory of Power Transmission Equipment & System Security and New Technology College of Electrical Engineering, Chongqing University, Chongqing 400044, China
  • Volume
    21
  • Issue
    4
  • fYear
    2014
  • fDate
    Aug-14
  • Firstpage
    1926
  • Lastpage
    1932
  • Abstract
    The electrical characteristics of contaminated insulators wetted by natural fog are rarely reported at home and abroad. Based on natural fog observations for 4 years at Xuefeng Mountain testing station, the AC flashover performance of three units of polluted insulator strings wetted by natural fog was studied. The results show that there are some differences on the flashover voltage stress between results of field test and Baker et al. The AC flashover process of the polluted insulators mainly includes wetness of the contamination, formation of dry bands, burning and elongation of partial arc and flashover. Moreover, the wind velocity has influence the flashover performance of insulator strings.
  • Keywords
    Flashover; Insulators; Pollution; Stress; Surface contamination; Testing; Wind speed; AC flashoverperformance; Natural test station; fog; insulator; pollution; wind velocity;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.004214
  • Filename
    6878025