DocumentCode
27294
Title
Effect of environment factors on ac flashover performance of 3 units of polluted insulator strings under natural fog condition
Author
Dong, Binhong ; Jiang, Xinyang ; Zhang, Zhenhao ; Hu, Jiankun ; Hu, Qin ; Shu, Lei
Author_Institution
State Key Laboratory of Power Transmission Equipment & System Security and New Technology College of Electrical Engineering, Chongqing University, Chongqing 400044, China
Volume
21
Issue
4
fYear
2014
fDate
Aug-14
Firstpage
1926
Lastpage
1932
Abstract
The electrical characteristics of contaminated insulators wetted by natural fog are rarely reported at home and abroad. Based on natural fog observations for 4 years at Xuefeng Mountain testing station, the AC flashover performance of three units of polluted insulator strings wetted by natural fog was studied. The results show that there are some differences on the flashover voltage stress between results of field test and Baker et al. The AC flashover process of the polluted insulators mainly includes wetness of the contamination, formation of dry bands, burning and elongation of partial arc and flashover. Moreover, the wind velocity has influence the flashover performance of insulator strings.
Keywords
Flashover; Insulators; Pollution; Stress; Surface contamination; Testing; Wind speed; AC flashoverperformance; Natural test station; fog; insulator; pollution; wind velocity;