• DocumentCode
    2731319
  • Title

    Simulation of incipient transformer faults

  • Author

    Palmer-Buckle, Peter ; Butler, Karen L. ; Sarma, N.D.R. ; Kopp, Alvin

  • Author_Institution
    Power Syst. Autom. Lab., Texas A&M Univ., College Station, TX, USA
  • fYear
    1998
  • fDate
    9-12 Aug 1998
  • Firstpage
    50
  • Lastpage
    53
  • Abstract
    This paper adapts a method of modeling internal winding faults of three-phase power transformers for single-phase distribution transformers. The model which is compatible with the alternative transients program, ATP, allows the simulation of turn-to-earth and turn-to-turn faults on either windings of a single-phase, two-winding, distribution transformer. Results of staged internal winding faults of a distribution transformer are compared with the simulation results to validate the model. The experimental results were found to be comparable to those of the simulation
  • Keywords
    fault simulation; power system simulation; power system transients; power transformers; transformer windings; alternative transients program; incipient transformer faults; internal winding faults; single-phase distribution transformers; staged internal winding faults; turn-to-earth faults; turn-to-turn faults; Circuit faults; Costs; Gases; Oil insulation; Phase transformers; Power system modeling; Power system simulation; Power transformer insulation; Power transformers; Transfer functions;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Circuits and Systems, 1998. Proceedings. 1998 Midwest Symposium on
  • Conference_Location
    Notre Dame, IN
  • Print_ISBN
    0-8186-8914-5
  • Type

    conf

  • DOI
    10.1109/MWSCAS.1998.759433
  • Filename