DocumentCode :
273406
Title :
Accurate fault location of transmission lines using microprocessors
Author :
Jeyasurya, B. ; Rahman, M.A.
Author_Institution :
Indian Inst. of Technolog., Bombay, India
fYear :
1989
fDate :
11-13 Apr 1989
Firstpage :
13
Lastpage :
17
Abstract :
The author presents an accurate algorithm to estimate the location of a transmission line fault. This method uses the fundamental frequency voltages and currents measured at the line terminals. These measurements are not required to be synchronized and the algorithm does not involve any simplifying assumptions. The algorithm is accurate since it solves the sequence network of the equivalent power system directly. The algorithm is evaluated using a 345 kV, 160 mile transmission line model
Keywords :
fault location; microcomputer applications; power engineering computing; power transmission lines; 345 kV; algorithm; currents; equivalent power system; fault location; microprocessors; model; power engineering computing; sequence network; transmission lines; voltages;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power Protection, 1989., Fourth International Conference on
Conference_Location :
Edinburgh
Type :
conf
Filename :
20603
Link To Document :
بازگشت