Proper testing of protection systems ensures against false tripping and unnecessary outages
Author :
Peterson, Oliver ; Scharlach, Rogerio ; Baltazar, Cesar
Author_Institution :
Commonwealth Edison Co., Lombard, IL, USA
fYear :
2009
fDate :
21-26 June 2009
Firstpage :
70
Lastpage :
83
Abstract :
This paper discusses the role of three-phase primary injection testing as an important part of the substation commissioning process. Individually testing the components of a protective relay scheme is common practice. Many times, this testing is performed without looking at how the equipment under test interacts with all the other components of the protective relay scheme. Several relay misoperations can be avoided by executing an overall testing plan with all the interconnected components. Three-phase primary current injection tests can be easily performed during equipment commissioning and can detect mistakes that would otherwise only be detected when load is available. This paper describes the planning, execution, and analysis of results of three-phase primary injection tests.
Keywords :
relay protection; substation protection; transformer testing; protection system testing; relay protection scheme; substation commissioning process; three-phase primary injection testing; transformer testing; Circuit testing; Current transformers; Instrument transformers; Performance evaluation; Power system protection; Power system relaying; Power transformers; Protective relaying; System testing; Voltage; avoid misoperations; bus protection; current transformers; management of protection; testing and commissioning; testing procedures; through-fault; transformer protection; transformer testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 2009. PPIC '09. Conference Record of 2009 Annual
Conference_Location :
Birmingham, AL
ISSN :
0190-2172
Print_ISBN :
978-1-4244-3464-0
Electronic_ISBN :
0190-2172