DocumentCode
273452
Title
New development of third harmonic ground fault protection schemes for turbine-generator stator windings
Author
Weijian, Wang ; Xie Xiaping ; Xiling, Zhong
Author_Institution
Isinghua Univ., Beijing, China
fYear
1989
fDate
11-13 Apr 1989
Firstpage
250
Lastpage
253
Abstract
The third harmonic (150 Hz) equivalent circuit of turbine-generator stator windings is introduced. The sensitivity of various 150 Hz ground fault protection schemes for stator windings are analyzed in detail by using the equivalent circuits. A ne protection scheme with high sensitivity is deduced, whose technical characteristics have been proved in practical operation
Keywords
electric generators; fault currents; machine protection; stators; turbines; 150 Hz; equivalent circuits; stator windings; third harmonic ground fault protection schemes; turbine-generator;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power Protection, 1989., Fourth International Conference on
Conference_Location
Edinburgh
Type
conf
Filename
20652