• DocumentCode
    273452
  • Title

    New development of third harmonic ground fault protection schemes for turbine-generator stator windings

  • Author

    Weijian, Wang ; Xie Xiaping ; Xiling, Zhong

  • Author_Institution
    Isinghua Univ., Beijing, China
  • fYear
    1989
  • fDate
    11-13 Apr 1989
  • Firstpage
    250
  • Lastpage
    253
  • Abstract
    The third harmonic (150 Hz) equivalent circuit of turbine-generator stator windings is introduced. The sensitivity of various 150 Hz ground fault protection schemes for stator windings are analyzed in detail by using the equivalent circuits. A ne protection scheme with high sensitivity is deduced, whose technical characteristics have been proved in practical operation
  • Keywords
    electric generators; fault currents; machine protection; stators; turbines; 150 Hz; equivalent circuits; stator windings; third harmonic ground fault protection schemes; turbine-generator;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power Protection, 1989., Fourth International Conference on
  • Conference_Location
    Edinburgh
  • Type

    conf

  • Filename
    20652