    Analysis of ground protection of unit connected generators using third harmonics

  • Author

    Shiwen, Shi ; Binhua, Sun

  • Author_Institution
    Nanjing Inst. of Technol., China
  • fYear
    1989
  • fDate
    11-13 Apr 1989
  • Firstpage
    254
  • Lastpage
    258
  • Abstract
    On unit connected generators, ordinary zero sequence voltage relays used for stator winding protection against single phase ground fault can´t cover 100% of the stator winding, i.e. there is a dead zone at or near the generator neutral. With the increase of generator capacity, especially the application of inner water cooling technology, ground protection for 100% stator winding is required. Protection based on response to third harmonic voltage can reliably cover the dead zone of zero sequence voltage protection and together with it constitutes the stator´s 100% ground protection. Third harmonic ground protection can be realized in different ways. The authors deal with a protection scheme with additional compensation circuitry. It differs from the Kiskachi scheme in that amplitude and phase compensation circuitry are used so that the protection sensitivity is favorably improved. A comprehensive analysis of the scheme is made
  • Keywords
    electric generators; harmonics; machine protection; stators; amplitude compensation; ground protection; phase compensation circuitry; stator protection; third harmonics; unit connected generators;