DocumentCode
27349
Title
Controller Design and Implementation of Indirect Current Control Based Utility-Interactive Inverter System
Author
Sunjae Yoon ; Hyeongmin Oh ; Sewan Choi
Author_Institution
LSIS R&D Center, LS Ind. Syst. Co., Anyang, South Korea
Volume
28
Issue
1
fYear
2013
fDate
Jan. 2013
Firstpage
26
Lastpage
30
Abstract
The utility-interactive inverter with critical load should be able to provide critical loads with a stable and seamless voltage. This letter proposes an indirect current controller which does not include any nonlinear factors in the control block, so that the classical control theory can be applied to the controller design. Also, a phase-locked loop algorithm is proposed to maintain the constant frequency across the critical load during the unintentional islanding since the magnitude is well regulated, but the frequency may vary with the proposed controller. Further, an islanding detection method is proposed for the controller, which does not cause a change in magnitude and frequency of critical load voltage.
Keywords
control system synthesis; distributed power generation; electric current control; invertors; load regulation; phase locked loops; classical control theory; constant frequency; control block; controller design; indirect current control; islanding detection method; nonlinear factors; phase-locked loop algorithm; unintentional islanding; utility-interactive inverter system; Current control; Frequency control; Harmonic analysis; Inverters; Phase locked loops; Power harmonic filters; Voltage control; Anti-islanding; indirect current control; phase-locked loop (PLL); seamless transfer; utility-interactive inverter;
fLanguage
English
Journal_Title
Power Electronics, IEEE Transactions on
Publisher
ieee
ISSN
0885-8993
Type
jour
DOI
10.1109/TPEL.2012.2210247
Filename
6248727
Link To Document