DocumentCode
273748
Title
The feature of harmonic in time domain and the harmonic impedance coefficient ZFn of network
Author
He Shou Zeng
Author_Institution
Shandong Inst. of Coal Sci. Res.
fYear
1989
fDate
23-25 May 1989
Firstpage
337
Lastpage
342
Abstract
When the harmonic current of nonlinear electric equipment is injected into a network, a disturbance is formed. According to the IEC/TC-77(EMC) and other standards for power systems and plants, the disturbance´s degree can be expressed by the network harmonic voltage, resulting from the harmonic current injected into the network from electric equipment. It can also be expressed by U n/ U 1, the ratio of the N th harmonic voltage (RMS). This is also called the sine wave distortion factor of the N th harmonic voltage, designated DF n%. A different coefficient ZF n is proposed that is the ratio of the harmonic voltage of the network bus (RMS) to the harmonic current injected into the network system. An example of its application is presented. It is claimed that compared to the general voltage distortion factor DF n%, ZF n can show electromagnetic compatibility more clearly
Keywords
distribution networks; electromagnetic compatibility; electromagnetic interference; EMC; electromagnetic compatibility; harmonic current; harmonic impedance coefficient; network bus; network harmonic voltage; nonlinear electric equipment; power systems; voltage distortion factor; Electromagnetic compatibility; Electromagnetic measurements; Harmonic analysis; Harmonic distortion; Impedance; Intelligent networks; Production facilities; Time domain analysis; Time measurement; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electromagnetic Compatibility, 1989., IEEE 1989 National Symposium on
Conference_Location
Denver, CO
Type
conf
DOI
10.1109/NSEMC.1989.37203
Filename
37203