DocumentCode
2738263
Title
Improvements in protection and commissioning of digital transformer relays at medium voltage industrial facilities
Author
Mozina, Charles J.
Author_Institution
Beckwith Electr. Co., Inc., Largo, FL, USA
fYear
2011
fDate
19-23 June 2011
Firstpage
96
Lastpage
105
Abstract
The application of multifunction digital relays to protect medium voltage power transformers has become a common industrial practice. Industrial transformers, unlike utility transformers, frequently use neutral grounding resistors to limit ground current during faults to 200-400A range on medium voltage systems. This paper will discuss why these types of transformers require sensitive ground differential protection. The paper will also discuss the basics of transformer protection including: phasing standards, through-fault withstand capability, differential/fusing/overcurrent protection, slope, CT requirements, harmonic restraint, and communicating these requirements properly when programming and commissioning new digital relays. The rationale for providing transformer overexcitation protection on all major transformers within industrial facilities is also addressed. Advancements in digital technology have allowed relay manufacturers to include more and more relay functions within a single hardware platform as well as address more and more transformer winding configurations. This has resulted in digital transformer relays requiring an experienced protection engineer to set and an experienced relay testing technician to commission. Since there are fewer experienced professionals among us now, the next generation of transformer relays needs to concentrate on this complexity issue in addition to technical improvements. This paper addresses these issues that the author believes are the major shortcomings of existing digital transformer protective relays.
Keywords
earthing; industrial plants; power transformer protection; relay protection; transformer windings; current 200 A to 400 A; digital transformer relay; ground differential protection; industrial transformer; medium voltage industrial facility; medium voltage power transformer protection; multifunction digital relay; relay testing; transformer overexcitation protection; transformer winding; Digital relays; Grounding; Oil insulation; Power transformer insulation; Windings; ANSI; IEC; V/Hz; electro-mechanical relays; harmonic restraint; inrush; low resistance grounding; multifunction digital relay; overexcitation; slope;
fLanguage
English
Publisher
ieee
Conference_Titel
Pulp and Paper Industry Technical Conference (PPIC), Conference Record of 2011 Annual IEEE
Conference_Location
Nashville, TN
ISSN
0190-2172
Print_ISBN
978-1-61284-272-1
Type
conf
DOI
10.1109/PPIC.2011.5982883
Filename
5982883
Link To Document