DocumentCode
2739301
Title
Power factor correction in AC/DC converters: design and measuring problems
Author
Papanikolaou, N.P. ; Polyzos, N.P. ; Tatakis, E.C.
Author_Institution
Dept. of Electr. & Comput. Eng., Patras Univ., Greece
Volume
1
fYear
1998
fDate
14-18 Oct 1998
Firstpage
222
Abstract
This paper presents the design and the real characteristics of a power factor correction (PFC) boost converter, operating at a power level of 1000 W and at a variable switching frequency (between 7 kHz and 100 kHz). The harmonic content of the input current of a PFC boost converter is monitorized and compared with the harmonic content of the input current of the traditional AC/DC conversion topology. Another issue that is discussed in this paper is the accuracy of different measuring instruments in function to the harmonic content of the measuring signal and the interference in the operational characteristics of this converter due to the presence of these instruments. Experimental results for the case of a traditional AC/DC converter as well as for the case of a PFC converter are exhibited
Keywords
AC-DC power convertors; power conversion harmonics; power factor correction; switching circuits; 1000 W; 7 to 100 kHz; AC/DC converters; boost converter; input current harmonic content; interference; measuring instruments accuracy; power factor correction; variable switching frequency; Analog-digital conversion; DC-DC power converters; Instruments; Interference; Monitoring; Power factor correction; Power measurement; Switching converters; Switching frequency; Topology;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power Proceedings, 1998. Proceedings. 8th International Conference On
Conference_Location
Athens
Print_ISBN
0-7803-5105-3
Type
conf
DOI
10.1109/ICHQP.1998.759890
Filename
759890
Link To Document