• DocumentCode
    2739632
  • Title

    Application of Dynamic Feed-forward with Lead-leg Component to Thermal Processes in Power Station

  • Author

    Fang, Fang ; Le Wei ; Tan, Wen ; Liu, Jizhen

  • Author_Institution
    Dept. of Autom., North China Electr. Power Univ., Beijing
  • Volume
    2
  • fYear
    0
  • fDate
    0-0 0
  • Firstpage
    7632
  • Lastpage
    7635
  • Abstract
    The essential characters of dynamic feed-forward with lead-leg component are analyzed. Three conclusions are deduced: (1) when subjected to a partial ramp input, the accumulative area of output is independent of the ramp ratio, but it is only associated with the gain of the input and the lead-leg coefficients. (2) For a ramp input and a step input with the same gain, the two output accumulative areas are equal. (3) The ramp ratio only influences the peak value and the settling time of output. The dynamic feed-forward with lead-leg component has been successfully applied to the coordinated control system of #4 power unit in Da La-te power plant. Field tests reveal that the load tracking performance of #4 power unit has been improved effectively
  • Keywords
    feedforward; power system control; thermal power stations; Da La-te power plant; coordinated control system; dynamic feedforward; lead-leg component; load tracking; partial ramp input; power station; thermal processes; Automation; Control systems; Feedforward systems; Independent component analysis; Intelligent control; Power generation; Testing; coordinated control system; dynamic feed-forward; lead-leg component; ramp input;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Intelligent Control and Automation, 2006. WCICA 2006. The Sixth World Congress on
  • Conference_Location
    Dalian
  • Print_ISBN
    1-4244-0332-4
  • Type

    conf

  • DOI
    10.1109/WCICA.2006.1713451
  • Filename
    1713451