DocumentCode
2739632
Title
Application of Dynamic Feed-forward with Lead-leg Component to Thermal Processes in Power Station
Author
Fang, Fang ; Le Wei ; Tan, Wen ; Liu, Jizhen
Author_Institution
Dept. of Autom., North China Electr. Power Univ., Beijing
Volume
2
fYear
0
fDate
0-0 0
Firstpage
7632
Lastpage
7635
Abstract
The essential characters of dynamic feed-forward with lead-leg component are analyzed. Three conclusions are deduced: (1) when subjected to a partial ramp input, the accumulative area of output is independent of the ramp ratio, but it is only associated with the gain of the input and the lead-leg coefficients. (2) For a ramp input and a step input with the same gain, the two output accumulative areas are equal. (3) The ramp ratio only influences the peak value and the settling time of output. The dynamic feed-forward with lead-leg component has been successfully applied to the coordinated control system of #4 power unit in Da La-te power plant. Field tests reveal that the load tracking performance of #4 power unit has been improved effectively
Keywords
feedforward; power system control; thermal power stations; Da La-te power plant; coordinated control system; dynamic feedforward; lead-leg component; load tracking; partial ramp input; power station; thermal processes; Automation; Control systems; Feedforward systems; Independent component analysis; Intelligent control; Power generation; Testing; coordinated control system; dynamic feed-forward; lead-leg component; ramp input;
fLanguage
English
Publisher
ieee
Conference_Titel
Intelligent Control and Automation, 2006. WCICA 2006. The Sixth World Congress on
Conference_Location
Dalian
Print_ISBN
1-4244-0332-4
Type
conf
DOI
10.1109/WCICA.2006.1713451
Filename
1713451
Link To Document