DocumentCode
2740304
Title
Application of ion earthing electrode and anti-corrosion synthetical reconstruction technique in reconstruction of grounding grids
Author
Lu, JiaZheng ; Yang, Li ; Zhang, HongXian ; Fang, Zhen ; Li, Bo ; Jiang, Zhenglong
Author_Institution
Technol. Lab., Hunan Electr. Power Corp. Res. Inst., Changsha, China
fYear
2011
fDate
1-4 Nov. 2011
Firstpage
562
Lastpage
566
Abstract
Grounding grids play an important role in guarantee the safe operation when the station has encountered the short circuit or be attacked by lighting. Grounding grids must reconstruct when grounding resistance does not meet the regulation requirements. Using ion earthing electrode to reconstruct the grounding grid will cost less and have better effect. However, this way may increase the corrosion of grounding grid. In this paper, “ Ion earthing electrode with anti-corrosion” grounding grid reconstruction technique is presented. This technique not only exerts the advantages of ion earthing electrode but also prevents grounding grid from corrosion. It was applied in 500kV Aijiachong power station, 220kV Nanzhutang power station, and so on. Grounding resistances of these power stations reached prospective effect after reconstruction.
Keywords
corrosion protection; earthing; anticorrosion synthetical reconstruction technique; grounding grids; ion earthing electrode; voltage 220 kV; voltage 500 kV; Conductivity; Corrosion; Electrodes; Grounding; Resistance; Soil; Substations; Ion earthing electrode; anti-corrosion; grounding grid; grounding resistance; reconstruction;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4577-1467-2
Type
conf
DOI
10.1109/APL.2011.6110147
Filename
6110147
Link To Document