DocumentCode :
2740343
Title :
Comparison of numerical analysis models for shielding failure of transmission lines
Author :
Wang, Xi ; He, Jinliang ; Peng, Xiangyang ; Li, Zhifeng
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
fYear :
2011
fDate :
1-4 Nov. 2011
Firstpage :
376
Lastpage :
380
Abstract :
The shielding failure is the occurrence of a lightning stroke that bypasses the overhead shielding wires and strikes on the phase conductors. The accurate design to improve the shielding effect of transmission line to lightning is one of key problems in transmission line design. Some numerical analysis models for analysis of shielding failure performance were proposed and discussed, mainly including the traditional electrogeometric model (EGM) and improved EGM, the leader progression model (LPM). The paper compares the results of lightning current range and location region for shielding failure by numerical calculation applying the three models. The influence of ground slope angle and voltage class of transmission line is also taken into account.
Keywords :
lightning protection; numerical analysis; power transmission lines; shielding; electrogeometric model; ground slope angle; leader progression model; lightning stroke; numerical analysis models; overhead shielding wires; phase conductors; shielding failure; transmission lines; Analytical models; Conductors; Lightning; Numerical analysis; Numerical models; Power transmission lines; Wires; EGM; LPM; shielding failure;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location :
Chengdu
Print_ISBN :
978-1-4577-1467-2
Type :
conf
DOI :
10.1109/APL.2011.6110149
Filename :
6110149
Link To Document :