Abstract
For the first time, a three-dimensional finite difference method (3D FDM) is adopted to simulate the potential distribution during grounding resistance measurements around an L-shape building under different directions and electrodes arrangements. The results show that the distributions of zero potential region with different measurement points and measurement electrodes arrangements are strikingly different when using a straight-line-three-probes method. To obtain more accurate measurement results, scientific and suitable measurement point locations should be properly chosen for the grounding resistance measurement of L-shape buildings according to the surrounding conditions in practical measurements.
Keywords
earth electrodes; electric resistance measurement; finite difference methods; lightning protection; L-shape building base; electrode arrangement; grounding resistance measurement; measurement electrode arrangement; potential distribution; straight-line-three-probe method; three-dimensional finite difference method; zero potential region; Buildings; Electric potential; Electrical resistance measurement; Electrodes; Grounding; Resistance; Soil; grounding resistance measurement; large-scale irregular grounding system; potential distribution; three-dimensional finite difference method;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4577-1467-2
Type
conf
DOI
10.1109/APL.2011.6110171
Filename
6110171
Link To Document