DocumentCode
2742289
Title
Calculation of lightning-induced voltages on an overhead line taking into account the presence of nearby buildings
Author
Borghetti, Alberto ; Napolitano, Fabio ; Nucci, Carlo Alberto ; Paolone, Mario
Author_Institution
Dept. of Electr. Eng., Univ. of Bologna, Bologna, Italy
fYear
2011
fDate
1-4 Nov. 2011
Firstpage
833
Lastpage
839
Abstract
For the case of urban overhead lines, the presence of nearby buildings is expected to affect the overvoltages induced by nearby lightning return strokes. This effect until now has been seldom taken into account in the literature on the subject. The paper presents a 3D FEM model that calculates the lightning electromagnetic pulse (LEMP) taking into account the presence of building placed in proximity of the LEMP-coupled overhead line. As a first approximation, the building surfaces are assumed as perfect conductors. Also the finite ground conductivity is neglected. The calculated fields are then introduced in the Agrawal et al. coupling model for the calculation of the induced voltages. The preliminary results of a sensitivity analysis carried by varying the dimensions of the building, its distance to the line and the position of the lightning stroke location are presented and discussed.
Keywords
electromagnetic pulse; finite element analysis; lightning protection; overvoltage protection; power overhead lines; 3D FEM model; LEMP-coupled overhead line; building surface; coupling model; finite ground conductivity; lightning electromagnetic pulse; lightning-induced voltage; nearby lightning return stroke; sensitivity analysis; Buildings; Conductors; Electric fields; Finite element methods; Lightning; Mathematical model; Surges;
fLanguage
English
Publisher
ieee
Conference_Titel
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4577-1467-2
Type
conf
DOI
10.1109/APL.2011.6110243
Filename
6110243
Link To Document