DocumentCode
2743754
Title
Investigation of systematic errors of an AC Josephson Voltage Standard
Author
Filipski, Piotr S.
Author_Institution
Nat. Res. Council Canada - INMS, Ottawa, ON, Canada
fYear
2012
fDate
1-6 July 2012
Firstpage
36
Lastpage
37
Abstract
This paper presents results of experiments quantifying two systematic errors associated with the calibrations by use of an AC Josephson Voltage Standard: the change in the voltage leads error with the change in the level of probe immersion in the liquid helium, and the effect of the internal inductance of a Josephson array. The measurements were performed at frequencies 100 kHz and above, however, they can be used in evaluating an error budget at lower frequencies.
Keywords
Josephson effect; calibration; inductance; liquid helium; measurement errors; measurement standards; superconducting arrays; voltage measurement; AC Josephson voltage standard; Josephson array; calibration; frequency 100 kHz; inductance effect; liquid helium; probe immersion; systematic error; voltage lead error; Arrays; Helium; Inductance; Liquids; Probes; Standards; Voltage measurement; Digital-analog conversion; Josephson arrays; measurement uncertainty; quantization; signal synthesis; standards; voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Precision Electromagnetic Measurements (CPEM), 2012 Conference on
Conference_Location
Washington, DC
ISSN
0589-1485
Print_ISBN
978-1-4673-0439-9
Type
conf
DOI
10.1109/CPEM.2012.6250646
Filename
6250646
Link To Document