    Practical validation for the frequency domain approach to study the thermal behavior of transformers under nonsinusoidal operation conditions

  • Author

    Delaiba, Antonio C. ; De Oliveira, José C. ; Cardoso, José R. ; Ribeiro, Paulo F.

  • Author_Institution
    Dept. of Electr. Eng., Fed. Univ. of Uberlandia, Brazil
  • Volume
    2
  • fYear
    1998
  • fDate
    14-18 Oct 1998
  • Firstpage
    946
  • Abstract
    This paper is focused in the direction of practical and theoretical aspects of thermal performance of transformers under distorted operating conditions. Using the superposition method, the thermal conditions are estimated through the frequency domain technique. To validate the theoretical results, practical measurements are made using a 15 kVA transformer prototype supplying a 6 pulse rectifier. The results are then used to validate the proposed method to investigate transformer thermal behavior
  • Keywords
    harmonic distortion; power supply quality; power system harmonics; power transformers; rectifying circuits; thermal analysis; 15 kVA; 6 pulse rectifier; eddy current losses; frequency domain approach; harmonic distortion; hysteresis losses; nonsinusoidal operation conditions; power quality; power transformers; superposition method; thermal behavior; thermal conditions estimation; transformer thermal behavior; winding losses; Distortion measurement; Eddy currents; Frequency domain analysis; Magnetic hysteresis; Pollution measurement; Power system harmonics; Pulse measurements; Pulse transformers; Rectifiers; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power Proceedings, 1998. Proceedings. 8th International Conference On
  • Conference_Location
    Athens
  • Print_ISBN
    0-7803-5105-3
  • Type

    conf

  • DOI
    10.1109/ICHQP.1998.760169
  • Filename
    760169