    A reactive power standard, based on the current comparator power bridge, established at CEPRI, for calibrating active/reactive power/energy meters under sinusoidal conditions is described. It allows calibration of active/reactive power and energy meters at voltages between 60 V to 600 V and currents between 0.1 A to 200 A, any power factor from zero lag through unity to zero lead, and test frequencies of 45 Hz to 65 Hz. The Type B uncertainty of the reactive power standard is estimated to be 30 μvar/VA at k = 2. A comparison of reactive power meter calibrations between CEPRI and NRC will also be presented and discussed, including the sources of errors and corresponding uncertainties.
  • Keywords
    calibration; electricity supply industry; power meters; reactive power; CEPRI; China electric power research institute; NRC; active-reactive power-energy meters; current 0.1 A to 200 A; current comparator power bridge; frequency 45 Hz to 65 Hz; reactive power-energy standard; type b uncertainty; voltage 60 V to 600 V; Bridge circuits; Calibration; Capacitors; Reactive power; Standards; Uncertainty; Voltage measurement; Current-comparator; power bridge; power standard; uncertainty;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Precision Electromagnetic Measurements (CPEM), 2012 Conference on
  • Conference_Location
    Washington, DC
  • ISSN
    0589-1485
  • Print_ISBN
    978-1-4673-0439-9
  • Type

    conf

  • DOI
    10.1109/CPEM.2012.6250693
  • Filename
    6250693