• DocumentCode
    2747451
  • Title

    Development of High-rate Discharge Stationary VRLA Battery

  • Author

    Tsujikawa, Tomonobu ; Yabuta, Kaho ; Matsushita, Takashi

  • Author_Institution
    NTT Facilities Inc., Tokyo
  • fYear
    2006
  • fDate
    10-14 Sept. 2006
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    NTT Facilities, Inc. has developed high-rate discharge stationary VRLA batteries (2 V, 200 Ah and 2 V, 300 Ah) for UPSs and data center backups. The battery capacities are 1.35-6.4 times greater at a discharge current of 1-3 CA compared with a conventional battery due to improved plates and poles. We reduced the masses of the batteries by 26% and the volumes by 47% for heavy-current discharges in a short time (10 minutes). In this way, the batteries were miniaturized, and the installation spaces were reduced. Moreover, the results of a life test showed that the lifetimes of the batteries can be extrapolated to more than 10 years at an ambient temperature of 25 degC and discharge currents of 2-3 CA. A vibration test showed that the batteries have earthquake-proof performance at an acceleration of 1.2 G
  • Keywords
    dynamic testing; lead acid batteries; NTT Facilities Inc; UPS; data center backups; earthquake-proof performance; stationary VRLA battery; vibration test; Assembly; Batteries; Fires; Iron; Life testing; Materials testing; Particle separators; Surface discharges; Surface resistance; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2006. INTELEC '06. 28th Annual International
  • Conference_Location
    Providence, RI
  • Print_ISBN
    1-4244-0430-4
  • Electronic_ISBN
    1-4244-0431-2
  • Type

    conf

  • DOI
    10.1109/INTLEC.2006.251632
  • Filename
    4018134