Title :
Safety and reliability of medium voltage switchgear with solid insulation of present day and future design
Author :
Menheere, W.M.M. ; Noordhuis, B.
Author_Institution :
Holec, Hengelo, Netherlands
Abstract :
The authors give a review of the design philosophy of insulation-enclosed switchgear. Attention is paid to specific requirements for the insulation enclosure as laid down in IEC standards, in order to guarantee safety and reliability during its life time. Experience with this system, acquired over many years of service, is described. The authors then give a short description of the use of epoxy resin for a future RMU design, equipped with an integrated earthing system, full range fuses, vacuum load-break switches or alternatively vacuum circuit-breakers. The maintenance requirements and the area of application are specified. They also make some remarks concerning the Dutch cable network and its reliability, as well as some general comments on switchgear and the environment
Keywords :
insulating materials; reliability; safety; switchgear; Dutch cable network; IEC standards; epoxy resin; fuses; integrated earthing system; maintenance; medium voltage switchgear; reliability; ring main unit; safety; solid insulation; vacuum circuit-breakers; vacuum load-break switches;
Conference_Titel :
Distribution Switchgear, 1990., Third International Conference on Future Trends in
Conference_Location :
London
Print_ISBN :
0-85296-396-3