Title :
Distance relay over-reaching due to TCSC presence on second circuit of double circuit line considering MOV operation
Author :
Kazemi, A. ; Jamali, S. ; Shateri, H.
Author_Institution :
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran
Abstract :
This paper discusses distance relays over-reaching in the presence of thyristor controlled series compensator (TCSC), one of the series connected flexible alternating current transmission system (FACTS) devices, on the far end of the second circuit of a double circuit transmission line, considering MOV operation. This is done by means of presenting the measured impedance at the relaying point and the ideal tripping characteristic. The measured impedance by distance relay is greatly influenced in the presence of TCSC on the line or even in the case of installing TCSC on the far end of the second circuit. The measured impedance depends on many factors including power system structural and operational conditions, the ground fault resistance, and TCSC compensation degree.
Keywords :
flexible AC transmission systems; power transmission faults; relay protection; thyristor applications; FACTS; MOV operation; TCSC; distance relay over-reaching; double circuit transmission line; flexible alternating current transmission system; ground fault resistance; metal oxide varistor; power system structural conditions; thyristor controlled series compensator; Control systems; Electrical resistance measurement; Flexible AC transmission systems; Flexible printed circuits; Impedance measurement; Power capacitors; Power system relaying; Protective relaying; Thyristors; Transmission line measurements; Distance Protection; Double circuit line; FACTS devices; MOV; Measured impedance; TCSC;
Conference_Titel :
Electrotechnical Conference, 2008. MELECON 2008. The 14th IEEE Mediterranean
Conference_Location :
Ajaccio
Print_ISBN :
978-1-4244-1632-5
Electronic_ISBN :
978-1-4244-1633-2
DOI :
10.1109/MELCON.2008.4618523