Experimental verifications on the electrical continuity and mechanical strength for impulse current of the steelwork
Author :
Lee, Kihong ; Lee, Taiksueb
Author_Institution :
Land & Housing Inst., Daejeon, South Korea
fYear :
2011
fDate :
1-4 Nov. 2011
Firstpage :
901
Lastpage :
905
Abstract :
This paper verified the electrical continuity of steelwork and tested the endurance of the steel bars´ connection for lightning current in reinforced concrete apartments. It was proven that the steelwork in reinforced concrete apartment has electrical continuity with low resistance (below than 0.2 Ω. Also the installation of the steel bars as down-conductor must be very carefully implemented since it was proven that a poor connection between two reinforcement bars can easily cause serious damage of the concrete even with impulsive current of 50kA, 10/350 μs.
Keywords :
bars; lightning protection; mechanical strength; reinforced concrete; steel; steel industry; current 50 kA; down-conductor; lightning current; lightning protection system; mechanical strength; reinforced concrete apartment; steel bar connection; steelwork electrical continuity; steelwork impulse current; time 10 mus; time 350 mus; Conferences; Lightning; Continuity; Lightning; Lightning Protection System; Reinforced Concrete; Steel bar; Steelwork; Surge;