DocumentCode :
2757298
Title :
Multiple feedback loop control strategy for UPS system having active filter ability
Author :
Oueidat, M. ; Sadarnac, D.
Author_Institution :
Supelec Service EEI, Gif sur Yvette, France
fYear :
1996
fDate :
6-10 Oct 1996
Firstpage :
450
Lastpage :
453
Abstract :
A simple uninterruptible power supply (UPS) configuration having active power filter ability (APF) is proposed in this paper. The proposed device can be operated in two modes, APF in normal operation and backup power modes in case of failure of the utility source. The proposed device has the advantages of only one power stage, compactness, high power factor and the total harmonic distortion performance is improved. Computer simulations and experimental results obtained from a low power model (50 VA) are carried out to verify the control strategy of system. Finally, the authors present the transient performance at the moment of the change of operation mode
Keywords :
active filters; control system analysis computing; control system synthesis; feedback; harmonic distortion; power filters; power system harmonics; uninterruptible power supplies; voltage control; 50 MVA; THD; UPS system; active power filter; computer simulation; control simulation; high power factor; multiple feedback loop control strategy; total harmonic distortion; transient performance; voltage control design; Active filters; Analog-digital conversion; Batteries; Bridge circuits; Control systems; Feedback loop; Power harmonic filters; Power system harmonics; Uninterruptible power systems; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 1996. INTELEC '96., 18th International
Conference_Location :
Boston, MA
Print_ISBN :
0-7803-3507-4
Type :
conf
DOI :
10.1109/INTLEC.1996.573360
Filename :
573360
Link To Document :
بازگشت