Abstract :
This paper describes the valve regulated lead acid battery management system (VMS) which is designed to manage and control a standby battery´s needs rather than simply monitor the battery´s behavior. In order to accomplish this goal, the following system design objectives were initiated: perform discharge tests; normal response to emergency conditions; float charge using constant current; boost charge using constant current; temperature compensate float current; low voltage/battery disconnect; automatic operation/user friendly; local or remote data retrieval and override; invisible to load voltage; cost effective; noninvasive; and failsafe. The paper briefly describes what each design objective tries to accomplish and then describe in detail how the VMS accomplishes those objectives
Keywords :
compensation; electric variables control; lead; safety; secondary cells; testing; Pb; Pb-acid valve regulated battery; automatic operation; battery disconnect; battery management system; boost charge; constant current; cost effective; discharge tests; emergency conditions response; failsafe; float charge; float current; local data retrieval; low voltage disconnect; noninvasive; remote data retrieval; standby battery control; temperature compensation; user friendly; Automatic testing; Battery management systems; Control systems; Disaster management; Low voltage; Performance evaluation; System testing; Temperature; Valves; Voice mail;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 1996. INTELEC '96., 18th International
Conference_Location :
Boston, MA
Print_ISBN :
0-7803-3507-4
Type :
conf
DOI :
10.1109/INTLEC.1996.573378
Filename :
573378
Link To Document :
بازگشت