Abstract :
A previous experiment was performed to compare the aging effect of AC and DC high-voltage on the groundwall insulation of 13.8 kV Roebel bars [1]. For this purpose, Voltage Endurance Test (VET) was performed on twelve spare bars. Half of the test specimens were submitted to a voltage of 35 kVac, and failures occurred on all bars in less than 150 hours. For this experiment, a ratio of 1.7 between direct voltage and power frequency voltage (RMS) was used. The other half of the test specimens were then tested at a voltage of 59.5 kVdc. Further in this experiment, since none of the bars subjected to the DC VET had failed during a test period of more than 2000 hours, it was decided to perform an AC voltage endurance test on these bars. This paper presents the test results of a comparative AC voltage endurance test performed on new bars and on bars previously subjected to a long term DC VET.
Keywords :
ageing; bars; failure analysis; machine insulation; machine testing; partial discharges; stators; AC VET; AC high-voltage; AC voltage endurance test; DC VET; DC high-voltage; RMS; Roebel bars; aging effect; direct voltage-power frequency voltage; groundwall insulation; partial discharge; rotating machine; spare bars; stator bars; test specimens; voltage 13.8 kV; voltage 35 kV; voltage 59.5 kV; Bars; Heating; Insulation; Partial discharge measurement; Partial discharges; Temperature measurement; Voltage measurement; partial discharge; rotating machine; stator bar; voltage endurance test;
Conference_Titel :
Electrical Insulation (ISEI), Conference Record of the 2012 IEEE International Symposium on
Conference_Location :
San Juan, PR
Print_ISBN :
978-1-4673-0488-7
Electronic_ISBN :
1089-084X
DOI :
10.1109/ELINSL.2012.6251458