Title :
A special protection scheme for voltage stability prevention
Author :
Alzahawi, Tara ; Sachdev, Mohindar S. ; Ramakrishna, G.
Author_Institution :
Power Syst. Res. Group, Saskatchewan Univ., Saskatoon, Sask.
Abstract :
Voltage instability is closely related to the maximum load-ability of a transmission network. The energy flows on the transmission system depend on the network topology, generation and loads, and on the availability of sources that can generate reactive power. One of the methods used for this purpose is the voltage instability predictor (VIP). This relay measures voltages at a substation bus and currents in the circuit connected to the bus. From these measurements, it estimates the Thevenin´s equivalent of the network feeding the substation and the impedance of the load being supplied from the substation. This paper describes an extension to the VIP technique in which measurements from adjoining system buses and anticipated change of load are taken into consideration as well
Keywords :
power transmission protection; reactive power; relay protection; substation protection; Thevenin equivalent; maximum load-ability; network topology; protection scheme; reactive power generation; substation bus; transmission network; voltage instability predictor; voltage stability prevention; Availability; Current measurement; Network topology; Power generation; Power system protection; Power system relaying; Reactive power; Stability; Substations; Voltage;
Conference_Titel :
Electrical and Computer Engineering, 2005. Canadian Conference on
Conference_Location :
Saskatoon, Sask.
Print_ISBN :
0-7803-8885-2
DOI :
10.1109/CCECE.2005.1556989