DocumentCode :
2758365
Title :
Experimental studies of breakdown characteristics of a 12-kV arcing horn under a lightning impulse superimposed on AC voltage
Author :
Arnacha, Sunchai ; Kunakorn, Anantawat ; Yutthagowith, Peerawut ; Tuethong, Piyapon
Author_Institution :
Electr. Eng. Dept., King Mongkut´´s Inst. of Technol. Ladkrabang, Bangkok, Thailand
fYear :
2011
fDate :
1-4 Nov. 2011
Firstpage :
205
Lastpage :
208
Abstract :
This paper presents the studies of breakdown characteristics of a 12-kVarcing horn under a lighting impulse superimposed on an AC power frequency voltage at various angles. The lightning impulse is superimposed on the AC power frequency voltage at a phase angle varied from 0° to 360. The 12-kV arcing horn under test has dimension and configuration according to DIN 42531 standard. The critical breakdown voltages (Ub50%) with and without superposition of an impulse voltage on the AC voltage are investigated and made comparison. It is found that the statistical breakdown voltages are depended on the phase angle of the AC voltage superposed by the lightning impulse voltage. From the test results, the AC voltage affects the insulation level and it should be taken into account in an insulation design and insulation coordination.
Keywords :
arcs (electric); electric breakdown; lightning protection; AC power frequency voltage; DIN 42531 standard; arcing horn; breakdown characteristics; impulse voltage; insulation coordination; insulation design; insulation level; lightning impulse; statistical breakdown voltages; voltage 12 kV; Breakdown voltage; Insulation; Lightning; Low pass filters; Power transformer insulation; Voltage control; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Lightning (APL), 2011 7th Asia-Pacific International Conference on
Conference_Location :
Chengdu
Print_ISBN :
978-1-4577-1467-2
Type :
conf
DOI :
10.1109/APL.2011.6111104
Filename :
6111104
Link To Document :
بازگشت