DocumentCode :
2759163
Title :
Evaluation of a reserve time prediction algorithm for lead acid battery
Author :
Ng, Patrick K. ; Hirsch, Marc ; Nguyen, Trung V.
Author_Institution :
Bell Labs./Power Syst., Lucent Technol., Mesquite, TX, USA
fYear :
1996
fDate :
6-10 Oct 1996
Firstpage :
616
Lastpage :
623
Abstract :
An algorithm has been developed to predict the remaining available battery capacity when a power outage occurs in telecommunication power supplies. This algorithm was formulated based on electrochemical phenomena during discharge. The effects of surface area, voltage, acid concentration and temperature on capacity were also included. An evaluation of the algorithm was performed using a variety of batteries, both flooded and valve-regulated. The results showed good accuracy in predicting the remaining capacity. In application, the algorithm is part of a plant controller that monitors voltage, current and temperature of the batteries. State-of-charge data is calculated when a discharge is detected
Keywords :
electrochemistry; lead; secondary cells; telecommunication power supplies; uninterruptible power supplies; Pb; Pb-acid secondary batteries; acid concentration; discharge; electrochemical phenomena; flooded batteries; power outage; remaining capacity estimation; reserve time prediction algorithm; state-of-charge data; surface area; telecommunication UPS; temperature; valve-regulated batteries; voltage; Batteries; Current density; Electrodes; Laboratories; Prediction algorithms; Surface discharges; Surface resistance; Temperature; Testing; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, 1996. INTELEC '96., 18th International
Conference_Location :
Boston, MA
Print_ISBN :
0-7803-3507-4
Type :
conf
DOI :
10.1109/INTLEC.1996.573400
Filename :
573400