• DocumentCode
    2760608
  • Title

    Investigation of partial discharge signal propagation, attenuation and pattern recognition in a stator winding

  • Author

    Hudon, Claude ; Guuinic, Philippe ; Audoli, Main

  • Author_Institution
    Inst. de Recherche, Hydro-Quebec, Varennes, Que., Canada
  • Volume
    1
  • fYear
    1996
  • fDate
    16-19 Jun 1996
  • Firstpage
    201
  • Abstract
    Offline partial discharge measurements have been carried out on a 3.5 MVA, hydro-generator. Specific types of defects have been simulated at different locations of a phase winding. The resulting signal was monitored. A modified bar including a defect was either connected immediately at the winding terminal or on one of the coils end. The position of the connection was gradually moved away from the terminal, while monitoring the discharge activity from the external coupler. It was found that slot discharges and other simulated defects generated characteristic phase resolved partial discharge patterns (PRPD) easily distinguishable from internal discharge patterns. Results showed that discharge signal attenuation was significant even below 1 MHz. The severity of the defects created was not evaluated but it was found that PRPD recognition was a useful identification tool
  • Keywords
    electric breakdown; hydroelectric generators; insulation testing; machine insulation; machine testing; partial discharges; stators; 3.5 MVA; discharge activity; external coupler; hydro-generator; identification tool; insulation breakdown tests; internal discharge patterns; offline partial discharge measurements; partial discharge signal attenuation; partial discharge signal propagation; pattern recognition; phase resolved partial discharge patterns; stator winding; Attenuation; Bars; Coils; Monitoring; Partial discharge measurement; Partial discharges; Pattern recognition; Pollution measurement; Pulse measurements; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
  • Conference_Location
    Montreal, Que.
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-3531-7
  • Type

    conf

  • DOI
    10.1109/ELINSL.1996.549317
  • Filename
    549317