Abstract
The success of MV vacuum switchgear is based on the high performance of vacuum interrupters for clearances of up to 15 mm. Due to the vacuum specific flashover process, a degressive rise of the breakdown voltage with enlarging gap space is observed. This effect prevents the economic application of vacuum technology in high-voltage applications above 52 kV. Here, the authors investigate the breakdown voltage of double break arrangements because of the high performance of small vacuum gaps. A possible high voltage interrupter could consist of a static mid-electrode and two movable contact elements. Their aim is to show whether double (or multiple) breaks are able to increase the electric strength in a vacuum
Keywords
electric breakdown; electric strength; flashover; insulation testing; switchgear testing; vacuum interrupters; 15 mm; MV vacuum switchgear; breakdown voltage; double break arrangements; electric strength; flashover mechanism; gap space; movable contact elements; static mid-electrode; vacuum interrupters; Breakdown voltage; Electrodes; Flashover; Interrupters; Medium voltage; Pollution; Space technology; Steel; Vacuum breakdown; Vacuum technology;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location
Montreal, Que.
ISSN
1089-084X
Print_ISBN
0-7803-3531-7
Type
conf
DOI
10.1109/ELINSL.1996.549354
Filename
549354
Link To Document