DocumentCode
2776928
Title
Evaluation of MV-XLPE cables
Author
Benjaminsen, J.T. ; Faremo, H. ; Olsen, J.A. ; Mikkelsen, N.P. ; Olsson, L.
Author_Institution
Norwegian Electr. Power Res. Inst., Trondheim, Norway
Volume
2
fYear
1996
fDate
16-19 Jun 1996
Firstpage
592
Abstract
An extensive investigation of the long term wet ageing performance of MV-XLPE power cables was started by Nordic (Norway, Sweden, Denmark and Finland) utilities and cable manufacturers in 1990. Representatives from the manufacturers and utilities were members of the project Steering Committee. The investigations were performed by the Norwegian Electric Power Research Institute (EFI). The work was divided into two parts, a three years research part and two years accelerated long term wet ageing test. In the research part, a total of 5 km cable core of old and new constructions were tested. 3.8 km of this cable core were aged under wet conditions in EFI´s laboratories over a period of three years. The aim was to identify the effect of different ageing parameters in order to establish test procedures and evaluation criteria for accelerated long term testing of MV-XLPE power cables. Based on results from the research work, a two year accelerated long term test was proposed, and in the summer of 1993 the wet ageing of cables from 15 European cable manufacturers war started. In the autumn of 1995 these cables were tested to breakdown with an AC step test. 14 of the 15 cables met the requirement set by the Steering Committee
Keywords
XLPE insulation; ageing; electric breakdown; insulation testing; life testing; power cable insulation; power cable testing; 12 kV; AC step test; MV-XLPE power cables; accelerated tests; ageing parameters; cable core; evaluation criteria; insulation breakdown tests; long-term wet ageing performance; test procedures; Accelerated aging; Additives; Cable insulation; Dielectrics and electrical insulation; Electric breakdown; Insulation testing; Laboratories; Life estimation; Manufacturing; Production;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location
Montreal, Que.
ISSN
1089-084X
Print_ISBN
0-7803-3531-7
Type
conf
DOI
10.1109/ELINSL.1996.549415
Filename
549415
Link To Document