Title :
AC breakdown strength of N2, SF6 and a mixture of N2+SF6 containing a small amount of SF 6
Author :
Mardikyan, Kevork ; Kalenderli, Özcan ; Ersen, Orhan ; Canarslan, Ergun
Author_Institution :
Fac. Electr. Eng., Istanbul Tech. Univ., Turkey
Abstract :
AC breakdown strengths of N2, SF6 and a mixture of N2+SF6 containing 1% of SF6 were experimentally studied. For this purpose, 50 Hz AC breakdown voltages in both uniform and nonuniform fields up to a pressure of 400 kPa from 50 kPa were measured. Test results show that the addition of 1% of SF6 to nitrogen increases the breakdown voltage up to 250 kPa in a nonuniform field. The relative breakdown strength of the mixture with respect to components was also calculated in 50 Hz AC voltage. The analysis of Paschen curves reveals an improvement of 40% in the breakdown strength of mixture in uniform field but in nonuniform fields, the maximum AC breakdown voltage of the mixture is 24% lower than that of pure SF6
Keywords :
SF6 insulation; electric breakdown; electric strength; insulation testing; nitrogen; 24 kPa; 50 Hz; 50 to 400 kPa; AC breakdown strengths; N2; N2+SF6; Paschen curves; SF6; gaseous insulation tests; insulation breakdown testing; nonuniform fields; uniform fields; Breakdown voltage; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Gas insulation; Gases; Nitrogen; Pressure measurement; Sulfur hexafluoride; Testing;
Conference_Titel :
Electrical Insulation, 1996., Conference Record of the 1996 IEEE International Symposium on
Conference_Location :
Montreal, Que.
Print_ISBN :
0-7803-3531-7
DOI :
10.1109/ELINSL.1996.549456