  • Title

    Voltage balancing control of a current source inverter used for DC power transmission

  • Author

    Menzies, R.W. ; Sun, Yuming

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Manitoba Univ., Winnipeg, Man., Canada
  • fYear
    1990
  • fDate
    12-14 Aug 1990
  • Firstpage
    155
  • Abstract
    The modulation control discussed is able to eliminate the negative sequence voltage caused by the load imbalance. The effectiveness of the modulation control in eliminating the negative sequence is verified by simulation results. With the modulation control the application of a current source GTO inverter can be extended to supplying unbalanced remote loads without any other form of AC support. Filters for the third current harmonic may be required depending on the degree of the load imbalance
  • Keywords
    DC power transmission; closed loop systems; invertors; modulation; power convertors; voltage control; DC power transmission; GTO inverter; current source inverter; harmonic filters; load imbalance; modulation control; negative sequence voltage elimination; third current harmonic; unbalanced remote loads; voltage balancing control; AC generators; Bridge circuits; Control systems; Frequency; Phase modulation; Power transmission; Pulse inverters; Pulse width modulation inverters; Thyristors; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Circuits and Systems, 1990., Proceedings of the 33rd Midwest Symposium on
  • Conference_Location
    Calgary, Alta.
  • Print_ISBN
    0-7803-0081-5
  • Type

    conf

  • DOI
    10.1109/MWSCAS.1990.140675