DocumentCode
2792775
Title
The evaluation of fifty percent breakdown voltage across Iranian 400 kV transmission line insulators
Author
Vahidi, B. ; Abedi, M. ; Hosseinian, S.H.
Author_Institution
Dept. of Electr. Eng., Amirkabir Univ., Tehran, Iran
fYear
1991
fDate
8-12 Jul 1991
Firstpage
331
Abstract
The Iranian isokeraunic map developed by the authors is presented. A statistical analysis of tower footing resistances of 400 kV lines in the Iranian national grid is also presented. An attempt has been made to evaluate lightning fifty-percent breakdown voltage (V 50 ) across 400 kV insulators in Iran, according to obtained keraunic levels and probabilistic results of tower footing resistances. A comparison between calculated V 50 and V 50 of presently installed insulators of 400 kV lines in the Iranian transmission system is also presented
Keywords
insulators; lightning; power overhead lines; 400 kV; Iranian isokeraunic map; breakdown voltage; lightning; national grid; probabilistic results; statistical analysis; tower footing resistances; transmission line insulators; Breakdown voltage; Computer hacking; Dielectrics and electrical insulation; Equations; Flashover; Lightning; Poles and towers; Power overhead lines; Statistical analysis; Transmission lines;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
Conference_Location
Tokyo
Print_ISBN
0-87942-568-7
Type
conf
DOI
10.1109/ICPADM.1991.172065