DocumentCode
2793784
Title
The new research on air density correction factor [power line external insulation]
Author
Xin-Sheng, Wang ; Chong-Hui, Lu
Author_Institution
Dept. of Electr. Eng., Xi´´an Jiaotong Univ., Shaanxi, China
fYear
1991
fDate
8-12 Jul 1991
Firstpage
546
Abstract
The authors summarize the results of joint research into the influence of altitude and atmospheric conditions on the disruptive discharge of external insulation of power transmission apparatus. The same tests on the same configuration and with the same procedures were performed at different altitudes (23 m, 506 m, 1040 m, 1890 m, 2300 m, and 3650 m above sea level). It is shown that the flashover voltages of external insulation of electrical facilities decrease with increase of altitude and decrease of air density. The correction factors of relative air density obtained from test results are nearly equal to the present correction factors in the IEC 60-1 standards and GB311-83 Chinese standards
Keywords
flashover; insulation; insulators; power overhead lines; 23 to 3650 m; GB311-83 Chinese standards; IEC 60-1 standards; air density correction factor; altitude; atmospheric conditions; disruptive discharge; electrical facilities; external insulation; flashover voltages; Dielectrics and electrical insulation; Flashover; Government; Humidity; IEC standards; Insulation testing; Laboratories; Performance evaluation; Power transmission; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
Conference_Location
Tokyo
Print_ISBN
0-87942-568-7
Type
conf
DOI
10.1109/ICPADM.1991.172118
Filename
172118
Link To Document