• DocumentCode
    2793784
  • Title

    The new research on air density correction factor [power line external insulation]

  • Author

    Xin-Sheng, Wang ; Chong-Hui, Lu

  • Author_Institution
    Dept. of Electr. Eng., Xi´´an Jiaotong Univ., Shaanxi, China
  • fYear
    1991
  • fDate
    8-12 Jul 1991
  • Firstpage
    546
  • Abstract
    The authors summarize the results of joint research into the influence of altitude and atmospheric conditions on the disruptive discharge of external insulation of power transmission apparatus. The same tests on the same configuration and with the same procedures were performed at different altitudes (23 m, 506 m, 1040 m, 1890 m, 2300 m, and 3650 m above sea level). It is shown that the flashover voltages of external insulation of electrical facilities decrease with increase of altitude and decrease of air density. The correction factors of relative air density obtained from test results are nearly equal to the present correction factors in the IEC 60-1 standards and GB311-83 Chinese standards
  • Keywords
    flashover; insulation; insulators; power overhead lines; 23 to 3650 m; GB311-83 Chinese standards; IEC 60-1 standards; air density correction factor; altitude; atmospheric conditions; disruptive discharge; electrical facilities; external insulation; flashover voltages; Dielectrics and electrical insulation; Flashover; Government; Humidity; IEC standards; Insulation testing; Laboratories; Performance evaluation; Power transmission; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
  • Conference_Location
    Tokyo
  • Print_ISBN
    0-87942-568-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.1991.172118
  • Filename
    172118