• DocumentCode
    2796915
  • Title

    Final breakdown mechanism

  • Author

    Pélissou, S. ; Noirhomme, B. ; Parpal, J.-L.

  • Author_Institution
    Hydro-Quebec, Varennes, Que., Canada
  • fYear
    1991
  • fDate
    8-12 Jul 1991
  • Firstpage
    1177
  • Abstract
    Preliminary results on the final breakdown mechanism of XLPE (cross-linked polyethylene) insulated field-aged cables are presented. The main goal is to determine the conditions that lead to the growth of electrical trees from water trees. Samples peeled off from two 28 kV and well-characterized (density, impurity and water content, field-water-tree density, oxidation) cables are considered. Aging conditions were 10 kV/mm, 60 Hz, 0.05 M NaCl solution, and 22-23°C. The results indicate that after 8000 h of aging the lab-water-tree length reaches 65-70% of the sample thickness and is not much affected by the presence of field water trees. The influence of the physico-chemical properties and AC breakdown strength is also reported
  • Keywords
    ageing; cable insulation; electric breakdown of solids; organic insulating materials; polymers; power cables; 22 to 23 degC; 28 kV; 8000 h; AC breakdown strength; XLPE; ageing conditions; cross-linked polyethylene; density; electrical trees; field-water-tree density; final breakdown mechanism; impurity content; insulated field-aged cables; oxidation; physico-chemical properties; water content; Aging; Cable insulation; Degradation; Dielectrics and electrical insulation; Electric breakdown; Impurities; Laboratories; Oxidation; Testing; Trees - insulation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
  • Conference_Location
    Tokyo
  • Print_ISBN
    0-87942-568-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.1991.172287
  • Filename
    172287