• DocumentCode
    2797094
  • Title

    New partial discharge detection method for live power cable systems

  • Author

    Fukunaga, K. ; Tan, M. ; Takehana, H. ; Takahashi, T. ; Yoshida, S.

  • Author_Institution
    Fujikura Ltd., Tokyo, Japan
  • fYear
    1991
  • fDate
    8-12 Jul 1991
  • Firstpage
    1218
  • Abstract
    A novel partial discharge detector, the REDI (resonance-type high-frequency partial discharge) sensor, is developed for picking up the high-frequency components of partial discharge (PD) current pulses from live cable systems. This sensor was applied to initial AC breakdown tests of practical joints of XLPE (cross-linked polyethylene) insulated cables, and PD could be clearly observed in all cases (the minimum apparent charge was 5 pC with 275 kV cables). The phase characteristics of PD against the applied voltage changed just before the breakdown
  • Keywords
    cable insulation; electric breakdown of solids; organic insulating materials; partial discharges; polymers; power cables; 275 kV; AC breakdown tests; REDI; XLPE; insulated cables; partial discharge detection method; phase characteristics; power cable systems; resonance-type high-frequency partial discharge; Breakdown voltage; Detectors; Electric breakdown; Partial discharges; Polyethylene; Power cables; Resonance; Sensor phenomena and characterization; Sensor systems; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1991., Proceedings of the 3rd International Conference on
  • Conference_Location
    Tokyo
  • Print_ISBN
    0-87942-568-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.1991.172298
  • Filename
    172298