• DocumentCode
    2799101
  • Title

    Energy conservation with use of “soft-starter”

  • Author

    Rezek, A.J.J. ; Coelho, C.A.D. ; Cortez, J.A. ; Vicente, J.M.E. ; Abreu, J.P.G. ; Ramos, C.D. ; Megalhaes, C. ; da Silva, V.F.

  • Author_Institution
    EFEI/IEE/DET-DON, Itajuba, Brazil
  • Volume
    1
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    354
  • Abstract
    The authors describe how energy saving has been obtained by using the soft-starter to reduce the voltage applied to the motor. Iron losses are then reduced and energy saving is achieved. The use of an autotransformer instead of a soft-starter has enabled a high energy saving, because the additional losses due to the harmonic currents are not present in this case. Energy saving with no load motor has been about 11% by using the soft-starter and 25% when the autotransformer is used, for load torque proportional to speed and for constant torque loads. Energy saving is decreased when the load torque is increased. Energy saving has been obtained until a load torque of about 42% of the rated torque; for higher torques no energy conservation is achieved. So the results of this paper are useful only for low load conditions. When the autotransformer is used the power factor and efficiency are better than in the other cases
  • Keywords
    autotransformers; electric motors; energy conservation; load (electric); starting; autotransformer; energy conservation; energy saving; iron losses; load torque; low load conditions; motor starting; power factor; soft-starter; AC motors; Automatic programming; Energy conservation; Energy consumption; Induction motors; Inductors; Iron; Switches; Thyristors; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power, 2000. Proceedings. Ninth International Conference on
  • Conference_Location
    Orlando, FL
  • Print_ISBN
    0-7803-6499-6
  • Type

    conf

  • DOI
    10.1109/ICHQP.2000.897053
  • Filename
    897053