Title :
Influence of thermal ageing on transformer oil properties
Author :
Abdi, S. ; Boubakeur, A. ; Haddad, A.
Author_Institution :
Ecole Nat. Polytech., Algiers
fDate :
June 30 2008-July 3 2008
Abstract :
In this paper, we present the electrical and physic-chemical behaviours of oil in high voltage transformers, under thermal ageing. Continuous thermal ageing tests were made on transformer oil BORAK22 during 5000 hours at two different temperatures 80degC and 120degC. Here, every 500 hours, the dielectric losses factor, the relative permittivity and the resistivity were measured. Other properties such as the breakdown voltage, the acidity degree, the water content, the colour and the cinematic viscosity are measured before and after ageing. The obtained results of this investigation show that the thermal ageing affects greatly the properties of transformer oil.
Keywords :
ageing; dielectric losses; electric breakdown; electrical resistivity; permittivity; transformer oil; viscosity; acidity degree; breakdown voltage; cinematic viscosity; colour; dielectric losses factor; electrical properties; high voltage transformers; physic-chemical properties; relative permittivity; resistivity; temperature 120 degC; temperature 80 degC; thermal ageing tests; time 5000 h; transformer oil BORAK22; water content; Aging; Dielectric loss measurement; Dielectric losses; Dielectric measurements; Oil insulation; Permittivity measurement; Petroleum; Temperature; Testing; Voltage transformers;
Conference_Titel :
Dielectric Liquids, 2008. ICDL 2008. IEEE International Conference on
Conference_Location :
Futuroscope-Chasseneuil
Print_ISBN :
978-1-4244-1585-4
Electronic_ISBN :
978-1-4244-1586-1
DOI :