DocumentCode :
2808303
Title :
Investigation of various options to avoid false tripping of a primary distribution feeder: Part I - modeling and analysis
Author :
Dahal, Om P. ; Brahma, Sukumar M. ; Ranade, Satish J. ; Malahowski, R.J.
Author_Institution :
Klipsch Sch. of Electr. & Comput. Eng., New Mexico State Univ., Las Cruces, NM, USA
fYear :
2010
fDate :
26-28 Sept. 2010
Firstpage :
1
Lastpage :
6
Abstract :
This paper describes the simulation of a 34 kV feeder from Pacific Gas and Electric (PG&E)´s distribution network. This feeder has a problem of being disconnected due to relay operation at the time of energization. A simulation model is created using PSCAD/EMTDC®, and validated using the test results provided by PG&E. Based on the simulations, some observations about the phenomenon are made to get a deeper insight in to the problem. A simplified feeder model is also created and validated for quick modeling of other feeders on PG&E´s network.
Keywords :
distribution networks; PSCAD/EMTDC; Pacific Gas and Electric distribution network; false tripping; feeder model; primary distribution feeder; simulation model; voltage 34 kV; Resistance; Switches; Digital Fourier transform; power distribution system; transformer inrush; zero sequence current;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
North American Power Symposium (NAPS), 2010
Conference_Location :
Arlington, TX
Print_ISBN :
978-1-4244-8046-3
Type :
conf
DOI :
10.1109/NAPS.2010.5618972
Filename :
5618972
Link To Document :
بازگشت