Title :
The negative leader in transformer oil under impulse voltage
Author_Institution :
Fed. Sci. Centre, All-Russian Electrotech. Inst., Moscow
fDate :
June 30 2008-July 3 2008
Abstract :
The complex experimental studies of the discharge mechanism in transformer oil under negative polarity (NP) of the lightning impulse were carried out using alternative diagnostic methods. Novel data concerning propagation mechanism and parameters of the predischarge channels were obtained. The results indicate that oil breakdown both under negative and positive polarity similar in a number of properties to the breakdown in the long air gaps.
Keywords :
lightning; power transformer insulation; transformer oil; diagnostic methods; lightning impulse voltage; negative leader; oil breakdown; predischarge channels; propagation mechanism; transformer oil; Electric breakdown; Electrodes; Electrons; Hydrocarbons; Microchannel; Needles; Oil insulation; Optical propagation; Petroleum; Shock waves;
Conference_Titel :
Dielectric Liquids, 2008. ICDL 2008. IEEE International Conference on
Conference_Location :
Futuroscope-Chasseneuil
Print_ISBN :
978-1-4244-1585-4
Electronic_ISBN :
978-1-4244-1586-1
DOI :
10.1109/ICDL.2008.4622520