Title :
A study on the test of UPS by energy feedback method
Author :
Chen, J.F. ; Chu, C.L. ; Huang, C.L.
Author_Institution :
Dept. of Electr. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
fYear :
1991
fDate :
11-14 Jun 1991
Firstpage :
3015
Abstract :
In the life test of online uninterruptible power supply (UPS) systems, with heater used as a load, much energy will be wasted in the form of heat. To save energy and decrease the test cost of UPS, an energy feedback method is proposed. Using the utility system instead of the heater as load and the principle of parallel operation of transmission, the energy that will be dissipated is turned back to the utility systems. From the experimental results, the energy savings is approximately 82% in life test
Keywords :
electronic equipment testing; life testing; uninterruptible power supplies; UPS testing; energy feedback method; energy savings; experimental results; life test; parallel operation of transmission; test costs reduction; uninterruptible power supply; utility system as load; Circuit testing; Costs; Feedback; Heat engines; Life testing; Load flow; Transformers; Uninterruptible power systems; Voltage control; Waste heat;