DocumentCode :
2833168
Title :
Comparing power factor and displacement factor corrections based on IEEE Std. 18-2002
Author :
Zobaa, A.F.
Author_Institution :
Electr. Power & Machines Dept., Cairo Univ., Giza, Egypt
fYear :
2004
fDate :
12-15 Sept. 2004
Firstpage :
1
Lastpage :
5
Abstract :
This work presents a comparison of minimizing the voltage total harmonic distortion at a load bus where it is desired to maintain the displacement power factor or the power factor at a desired level. The performance is discussed by means of numerical examples taken from existing publications. Paybacks of less than one year can be expected. Finally, the major attribute of This work is that it, unlike conventional approaches, guarantees convergence to the optimal solution. This accomplishment is a direct result from the improvement in the algorithm in which provisions are made to identify and to avoid capacitor values, which would create resonance conditions, the problem formulation in which the effect of the transmission line impedance on the load voltage is included while calculating the optimal capacitor value, and frequency dependent nature of the supply source.
Keywords :
IEEE standards; harmonic distortion; load (electric); minimisation; power factor correction; power system harmonics; power transmission lines; IEEE Std. 18-2002; displacement factor corrections; load bus; load voltage; network harmonics; optimal capacitor value; optimization techniques; power factor conditioning; power factor corrections; total harmonic distortion; transmission line impedance; Capacitors; Current supplies; Distortion measurement; Power supplies; Power system harmonics; Reactive power; Resonance; Senior members; Total harmonic distortion; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power, 2004. 11th International Conference on
Print_ISBN :
0-7803-8746-5
Type :
conf
DOI :
10.1109/ICHQP.2004.1409319
Filename :
1409319
Link To Document :
بازگشت