• DocumentCode
    2836028
  • Title

    Failure of LV ASD supply-side fuses due to MV motor fuse operation

  • Author

    Van Coller, J.M. ; Beutel, A.A. ; Maphalala, N. ; Endrejat, F. ; Msimango, J.

  • Author_Institution
    Witwatersrand Univ., Johannesburg
  • fYear
    2006
  • fDate
    15-17 Dec. 2006
  • Firstpage
    1700
  • Lastpage
    1705
  • Abstract
    Transients in MV networks due to MV motor fuse operation can propagate through MV/LV transformers to LV networks. The LV surges can then cause the high-speed fuses protecting LV adjustable speed drives (ASDs) to operate and this can disrupt production. LV ASDs often include supply-side reactors to make them less susceptible to surges (in particular capacitor-switching surges). For the network studied, these reactors did not prevent operation of the particular ASD highspeed fuses. One possible reason was that the supply-side reactors were saturating during the surge conditions associated with MV fuse operation. This paper describes the investigation that included initial measurements, a simulation study so that various proposed solutions could be compared, and final measurements with the final recommended solution in place -supply-side reactors that did not saturate during these surge conditions.
  • Keywords
    capacitor switching; electric fuses; motor drives; variable speed drives; LV ASD supply-side fuses; MV motor fuse operation; adjustable speed drives; capacitor-switching surges; supply-side reactors; Africa; Circuit faults; Current measurement; Fuses; Inductors; Phase measurement; Surge protection; Transformers; Variable speed drives; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Technology, 2006. ICIT 2006. IEEE International Conference on
  • Conference_Location
    Mumbai
  • Print_ISBN
    1-4244-0726-5
  • Electronic_ISBN
    1-4244-0726-5
  • Type

    conf

  • DOI
    10.1109/ICIT.2006.372476
  • Filename
    4237798