• DocumentCode
    283713
  • Title

    The co-ordination of protection and auto-reclose on 11 kV distribution networks

  • Author

    Ong, C.H. ; Royle, J.B.

  • fYear
    1988
  • fDate
    1988
  • Abstract
    The authors describe the co-ordination between the main line auto-reclosing circuit breaker and the fuse protection of a spur of an 11 kV distribution network. The relay has an instantaneous overcurrent set at 300 A, an instantaneous earth fault set at 120 A and an overall fault clearance time of 0.1 seconds
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Improving Supply Security on 11kV Overhead Networks, IEE Colloquium on
  • Conference_Location
    London
  • Type

    conf

  • Filename