DocumentCode
283713
Title
The co-ordination of protection and auto-reclose on 11 kV distribution networks
Author
Ong, C.H. ; Royle, J.B.
fYear
1988
fDate
1988
Abstract
The authors describe the co-ordination between the main line auto-reclosing circuit breaker and the fuse protection of a spur of an 11 kV distribution network. The relay has an instantaneous overcurrent set at 300 A, an instantaneous earth fault set at 120 A and an overall fault clearance time of 0.1 seconds
fLanguage
English
Publisher
iet
Conference_Titel
Improving Supply Security on 11kV Overhead Networks, IEE Colloquium on
Conference_Location
London
Type
conf
Filename
209790
Link To Document