Optimum settings for the 100% ground-stator protection in the Tucurui, Balbina and Samuel hydro-power plants-Eletronorte-Brazil
Author
De Oliveira, A. J Soares ; de Miranda Aviz, C.A.
fYear
1993
fDate
1993
Firstpage
186
Lastpage
190
Abstract
One of the most upsetting problems reported during the commissioning and initial operation of the generator units installed in the Tucu-Rui, Balbina and Samuel hydroelectric power plants in the Amazon Basin-Brazil is related to the performance of the 100% ground-stator protection which method of detection is third harmonic-based. The authors present simple but efficient third harmonic monitoring techniques experimented by Eletronorte-BKP/Copertec for its correct evaluation in potential transformer secondaries connected to either the generator neutral or the generator terminals. As a result, the third harmonic content in a generator, as a boundless discriminator for faults close to the neutral, can be better criticized