    Optimum settings for the 100% ground-stator protection in the Tucurui, Balbina and Samuel hydro-power plants-Eletronorte-Brazil

  • Author

    De Oliveira, A. J Soares ; de Miranda Aviz, C.A.

  • fYear
    1993
  • fDate
    1993
  • Firstpage
    186
  • Lastpage
    190
  • Abstract
    One of the most upsetting problems reported during the commissioning and initial operation of the generator units installed in the Tucu-Rui, Balbina and Samuel hydroelectric power plants in the Amazon Basin-Brazil is related to the performance of the 100% ground-stator protection which method of detection is third harmonic-based. The authors present simple but efficient third harmonic monitoring techniques experimented by Eletronorte-BKP/Copertec for its correct evaluation in potential transformer secondaries connected to either the generator neutral or the generator terminals. As a result, the third harmonic content in a generator, as a boundless discriminator for faults close to the neutral, can be better criticized