Analysis of the operating regimes of a medium / low voltage transformer supplying a distribution network for urban transports
Author :
Nicolae, Petre-Marian ; Popa, Dinut-Lucian ; Voinea, Marius
Author_Institution :
Electr. Eng., Energetics & Aeronaut. Dept., Univ. of Craiova, Craiova, Romania
fYear :
2012
fDate :
25-27 Oct. 2012
Firstpage :
1
Lastpage :
4
Abstract :
A medium/low voltage transformer from a distribution substation for urban transports operating in a highly distorting regime is analyzed. Regimes of idle running, running with non-linear load, respectively fault (short-circuit) are presented from the theoretical point of view. The results yielded by their operation simulation using MATLAB / SIMULINK are discussed. Aspects related to the measurement and harmonic analysis of voltages and currents are analyzed, along with experimental results related to the highly distorted regime influence over the primary and secondary windings. Losses in distribution transformers due to non-linear loads resulting into (no-) load losses due to increased skin effect, eddy current, stray and losses through hysteresis with negative effects over the lifespan of the transformers and total costs are discussed too. As the analysis revealed that the harmonic content and reactive power must be diminished, some solutions are suggested. A relative cheap solution (not necessarily the best) is passive filtering. A more efficient solution for the compensation of the distorting regime is the active filtering, this being efficiently adaptable to the analyzed system´s operating regimes, resulting into power savings and transformer´s operation at the rated parameters. Another good solution is the substitution of old transformers (particularly sensitive to non-linear loads) by more efficient transformers.
Keywords :
active filters; eddy currents; harmonic analysis; passive filters; potential transformers; power distribution faults; power filters; reactive power; skin effect; substations; transformer windings; Matlab-Simulink; active filtering; distribution network; distribution substation; distribution transformer losses; eddy current; harmonic analysis; harmonic content; medium-low voltage transformer; nonlinear load losses; passive filtering; power savings; primary windings; reactive power; secondary windings; skin effect; stray losses; urban transports; voltage measurement; Circuit faults; Harmonic analysis; Power harmonic filters; Power quality; Rectifiers; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Applied and Theoretical Electricity (ICATE), 2012 International Conference on
Conference_Location :
Craiova
Print_ISBN :
978-1-4673-1809-9
Type :
conf
DOI :
10.1109/ICATE.2012.6403408
Filename :
6403408
Link To Document :
بازگشت