Title :
Predicting molded-case circuit breaker let-through characteristics in an electrical system under short-circuit conditions
Author :
Gregory, George D. ; Hall, William M.
Author_Institution :
Square D. Co., Cedar Rapids, IA, USA
fDate :
Sept. 28 1991-Oct. 4 1991
Abstract :
The authors discuss the MCCB (molded-cased circuit breaker) as a circuit element and describe one method of calculating system behavior with the MCCB as an element. Circuit breaker behavior in a system is determined using six parameters of the circuit breaker´s measured behavior. The proposed method satisfies any condition for power factor and closing angle of fault current level within the instantaneous operating range of the circuit breaker. As verified by tests, the method outputs conservative estimates of key circuit parameters relative to recommended values for safe applications.<>
Keywords :
circuit breakers; short-circuit currents; MCCB; circuit breaker; closing angle; fault current; let-through characteristics; moulded case; power factor; short-circuit; Arm; Circuit breakers; Data engineering; Delay; Design engineering; Industry Applications Society; Magnetic separation; Protection; Systems engineering and theory; Voltage;
Conference_Titel :
Industry Applications Society Annual Meeting, 1991., Conference Record of the 1991 IEEE
Conference_Location :
Dearborn, MI, USA
Print_ISBN :
0-7803-0453-5
DOI :
10.1109/IAS.1991.178099