• DocumentCode
    284459
  • Title

    Effects of multiple stroke lightning impulse currents on ZnO arresters

  • Author

    Darveniza, M. ; Mercer, D.R. ; Tumma, L.R.

  • Author_Institution
    Queensland Univ., St. Lucia, Qld., Australia
  • fYear
    1993
  • fDate
    17-21 May 1993
  • Abstract
    Multiple stroke lightning ground flashes can impose surges of exceptional severity on the arresters used to protect exposed distribution system equipment. The authors report laboratory studies of the effects of representative multiple impulse currents on zinc-oxide surge arresters of distribution type. The results indicate that sextuple 8/20 μs currents can cause damage to arresters not evident with standard lightning current tests
  • Keywords
    distribution networks; lightning protection; power system protection; surge protection; zinc compounds; 20 mus; 8 mus; ZnO; distribution system; ground flashes; multiple stroke lightning impulse currents; power system protection; surge protection;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 1993. CIRED. 12th International Conference on
  • Conference_Location
    Birmingham
  • Print_ISBN
    0-85296-561-3
  • Type

    conf

  • Filename