DocumentCode
2846381
Title
Dynamic Behavior of DFIG-Based Wind Turbines during Grid Faults
Author
Erlich, I. ; Wrede, H. ; Feltes, C.
Author_Institution
Duisburg-Essen Univ., Duisburg
fYear
2007
fDate
2-5 April 2007
Firstpage
1195
Lastpage
1200
Abstract
According to grid codes issued by utilities, tripping of wind turbines following grid faults is not allowed. Besides, to provide voltage support to the grid mandatory reactive current supply is necessary. To enable wind turbines ride-through low voltage periods special protection measures have to be implemented. In this paper the behavior of DFIG based wind turbines during grid faults is discussed and elucidated using simulation results. It is shown that with properly designed crowbar and DC-link chopper even zero voltage ride-through is possible.
Keywords
asynchronous generators; fault diagnosis; power grids; wind turbines; DC-link chopper; DFIG-based wind turbines; crowbar; doubly-fed induction generator; grid faults; grid mandatory reactive current supply; protection measures; Choppers; Current measurement; Current supplies; Induction generators; Low voltage; Power system stability; Protection; Stress; Wind energy; Wind turbines; Doubly-Fed Induction Generator; Fault-Ride Through; Wind Turbine;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Conversion Conference - Nagoya, 2007. PCC '07
Conference_Location
Nagoya
Print_ISBN
1-4244-0844-X
Electronic_ISBN
1-4244-0844-X
Type
conf
DOI
10.1109/PCCON.2007.373117